Floors
The values pass: why ask for recompaction?
100 MPa
EV2 moduli above 100 MPa against 50 required, and a recommendation to recompact with moistening, sent with the test report.
The constraints
A platform to check before slab pouring, at 3 measurement points, with a 50 MPa requirement on the EV2 modulus.
My role
Work-study test technician at EuroContrôle Qualité, from September 2024 to August 2025, handling about 50 assignments independently.
What I did
On site, static plate load tests (LCPC CT2 procedure, 600 mm plate, Benkelman beam, EV1 and EV2 moduli) and light dynamic plate tests.
In the lab, standard tests: methylene blue value, sieve analysis, immediate bearing index.
From these tests, soil classification to the French GTR 92 guide, to decide on reuse, treatment or rejection.
How I checked it
The EV2 moduli exceed the requirement, but the EV2/EV1 ratio exceeds 2.2. The two values have to be read together.